CHAPTER 6 USING THE COMMUNICATIONS FUNCTION
Parameter No.
00
PV monitor
01
Set point
04
MV monitor (heat)
42
MV monitor (cool)
14
Valve opening monitor
02
Alarm value 1
03
Alarm value 2
41
Alarm value 3
19
Proportional band
20
Integral time
21
Derivative time
22
Cooling coefficient
09
Dead band
87
Position-proportional dead
band
23
Manual reset value
06
Hysteresis (heat)
43
Hysteresis (cool)
07
Control period (heat)
08
Control period (cool)
17
Heater current monitor
18
Heater burnout alarm
46
LBA detection time
47
MV at reset
48
MV at PV error
50
MV upper limit
49
MV lower limit
51
MV change rate limit
56
Input digital filter
88
Open/close hysteresis
25
Alarm 1 hysteresis
26
Alarm 2 hysteresis
52
Alarm 3 hysteresis
53
Input shift upper limit
54
Input shift lower limit
*1 Possible only during reading
*2 During temperature input, the range becomes the range of use of the selected sensor.
*3 During heating and cooling control, the range becomes 0.0 to 105.0.
*4 During heating and cooling control, the range becomes -105.0 to 0.0.
*5 During position-proportional control, the range becomes 1 to 3999.
*6 During heating and cooling control, the range becomes -105.0 to 105.0.
During position-proportional control, you can select between 0: Hold/1: Open/2: Close. (Defaults is "0 : hold".)
6--8
Parameter
*1 *2
Scaling lower limit -10% to scaling upper limit +10%
*1
*1
*1
*1
*1
*6
*6
*3
*4
Data Setting and Monitor Range
Set point lower limit to set point upper limit
-5.0 to 105.0
0.0 to 105.0
-10.0 to 110.0
-1999 to 9999
-1999 to 9999
-1999 to 9999
0.1 to 999.9
0 to 3999
0 to 3999
0.01 to 99.99
-19.99 to 99.99
0.1 to 10.0
0.0 to 100.0
0.01 to 99.99
0.01 to 99.99
1 to 99
1 to 99
0.0 to 55.0
0.0 to 50.0
0 to 9999
-5.0 to 105.0
-5.0 to 105.0
MV lower limit +0.1 to 105.0
-5.0 to MV upper limit -0.1
0.0 to 100.0
0 to 9999
0.1 to 20.0
0.01 to 99.99
0.01 to 99.99
0.01 to 99.99
-199.9 to 999.9
-199.9 to 999.9