Parameter Structure - Omron E5EK PROGRAMMABLE TYPE User Manual

Digital controller (programmable type)
Table of Contents

Advertisement

CHAPTER 7 CALIBRATION

7.1 Parameter Structure

Thermocouple 1
Transfer output
Data storage
7--2
• To calibrate the E5EK-T controller, select [
play to select the calibration mode. [
• However, note that [
when, for example, the user is calibrating the E5EK-T controller for
the first time. If this happens, [
curity" parameter (protect mode) to "0".
• The parameters in the calibration mode are structure as follows:
Platinum resistance
Thermocouple
thermometer
Thermocouple 2
Only when the
transfer output
function is sup-
ported
• To select the desired parameter, press the
displayed in the following order:
Calibration of inputs → Calibration of transfer output →
Storage of calibration data
If the E5EK-T controller does not support the transfer output func-
tion, calibration of transfer output is automatically deleted from the
calibration procedure as follows:
Calibration of inputs → Storage of calibration data
• Only inputs that have been set in the "input type" parameter (setup
mode) can be calibrated. To temporarily store data for each of the cal-
ibration parameters, press the
• Transfer output can be calibrated only when the Communications
unit (E53-AKF) is set in the controller. To adjust data items, press the
or
keys.
• The data store menu is displayed only when all calibration items have
temporarily been stored.
• After calibrating input, you must always check indication accuracy.
For details, see page 7-12.
] may not be displayed on the menu display
] is displayed by changing the "se-
Current input
Thermocouple 1
: K1/J1/L1/E/N/W/PLII
Thermocouple 2
: K2/J2/L2/R/S/B/T/U
Platinum resistance
:JPt100/Pt100
thermocouple
key for 1 second.
] in the menu dis-
] .is displayed.
Voltage input
0 to 5V 1 to 5V
0 to 10V
key. Parameters are