Service And Maintenance; Replace The Fan - Siemens SINAMICS S220 Equipment Manual

Booksize power units
Hide thumbs Also See for SINAMICS S220:
Table of Contents

Advertisement

Motor Modules
8.5 Motor Modules 85 A, 132 A and 200 A
8.5.13

Service and maintenance

8.5.13.1

Replace the fan

Requirement
Electric shock when live parts are touched
You must switch off the supply voltages (400 V AC and 24 V DC) before replacing the fan. A
hazardous voltage (residual charge) is still present for up to 5 minutes after the power supply
has been switched off.
Contact with live parts can result in death or serious injury.
• Wait at least this long before starting work to replace the fan.
• Check that the drive line-up is in a no-voltage condition before removing the component.
Motor Modules have an operating hours counter (p0251) to determine when the fan needs
to be replaced, and a message (A30042) is output as soon as the maximum operating time is
reached. The fan modules of the Motor Modules can be ordered as replacement parts.
Only qualified personnel are permitted to install spare parts.
When replacing the fan, you must observe the ESD regulations.
Always use the following fan module when replacing the fan:
Table 8-43
Motor Module
Width
150 mm
200 mm
Required tools:
• T20 torx screwdriver
• Slotted screwdriver 0.8 x 5.5 mm
• Socket wrench size 13
242
WARNING
Fan modules for replacing a fan
Rated current
85 A, 132 A
200 A
Fan module
Article number
6SL5166-0AF00-0AA0
6SL5166-3AH00-0AA0
Equipment Manual, 09/2023, A5E53307519B AA
Fan rated voltage
48 V
48 V