Siemens SINAMICS S220 Equipment Manual page 210

Booksize power units
Hide thumbs Also See for SINAMICS S220:
Table of Contents

Advertisement

Motor Modules
8.4 Motor Modules 45 A and 60 A
Procedure
Figure 8-52
Proceed as follows to connect the shield of the motor connection cable to the shield
connection plate of the Motor Module:
1. Fasten the shield of the motor connection cable to the shield connection plate using a hose
clamp or a shield connection clamp according to the table below.
2. When fastening a shield connection clamp, ensure that the conductor is located at the center
of the clamp.
Component
Hose clamp
Shield connection clamp Phoenix SK 14
Shield connection clamp Phoenix SK 35
Result
You have routed the motor connection cable so that it is screened.
Figure 8-53
208
Mounting for shield connection clamp
Mounting for the hose clamp
Shield support options for Motor Modules 45 A and 60 A
Shield support with hose clamp (left), shield connection clamp (center) and three shield
connection clamps for single cores (right)
Tightening torque
0.8 ... 1 Nm (7.08 ... 8.85 lbf in)
0.8 Nm (7.08 lbf in)
1.8 Nm (15.93 lbf in)
Equipment Manual, 09/2023, A5E53307519B AA