Also note the following:
• For UL applications, only use UL-approved ring or pipe-type cable lugs (ZMVV) certified for the
particular voltage. The permissible current must be at least 125% of the input or output
current. Use the higher value as basis.
• For cables with a cross-section of 150 mm
a maximum cable lug width of 24 mm (e.g. from the Klauke company, article 10SG8), with
additional shrink-on sleeve to ensure touch protection.
8.5.12.3

Preparing the motor connection cable

Overview
Motors are connected to a Motor Module using a motor connection cable. You must first
fabricate these. If you are using MOTION-CONNECT power cables, then you must first assemble
them.
Requirement
NOTICE
Adherence to core and stripped lengths
If the specified core and stripped lengths are not complied with, single cores can be damaged
or shield contact prevented.
• Comply with the specified core and stripped lengths.