Siemens SINAMICS S220 Equipment Manual page 88

Booksize power units
Hide thumbs Also See for SINAMICS S220:
Table of Contents

Advertisement

Mounting
5.2 Layout of the components
Figure 5-6
For a multi-tier configuration, when connecting the DC link, observe the following additional
requirements:
• Locate the DC link adapter at the left-hand or right-hand side of the component.
• Only use single core and finely-stranded conductors. Use shielded single cores and connect
the cable shield at both ends. The cables must be routed so that a ground fault or short-circuit
is completely ruled out.
86
DC link adapter
Example of a three-tier configuration
Booksize power units
Equipment Manual, 09/2023, A5E53307519B AA

Advertisement