Procedure
Cores U-V-W
Protective conductor core
Protective braided shield
Shrink-on sleeve
Figure 7-12
Line supply cable for Smart Line Modules
Table 7-10
Core and stripped lengths as a function of the cable cross-section, data in mm and (inch)
Connection
Connection
plug
Plug with
U1, V1, W1
screw connec‐
tion
Protective conduc‐
tor
Plug with push-
U1, V1, W1
in connection
Protective conduc‐
tor
To connect the line supply cable at the connection plug, prepare these as subsequently
described:
1. Remove 110 mm (4.33 in) of cable sheath with a tolerance of ±5 mm (±0.20 in).
2. Shorten the protective braided shield and fold it back by the same length.
3. Fix the protective braided shield. Preferably use a shrink-on sleeve with hot melt adhesive.
4. Shorten the single cores to length "a" according to the table above. The stripped lengths of
the line supply cables are the same for all cross-sections.
5. Remove the insulation of the single cores to length "b" according to the table above.
Booksize power units
Equipment Manual, 09/2023, A5E53307519B AA
6 mm² AWG 10
a
b
90 +2/-3
12 ±0.5
(3.54+0.08/-0.12)
(0.47 ±0.02)
95 +2/-3
12 ±0.5
(3.74 +0.08/-0.12)
(0.47 ±0.02)
95 +2/-3
12 ±0.5
(3.74+0.08/-0.12)
(0.71 ±0.02)
100 +2/-3
12 ±0.5
(3.94 +0.08/-0.12)
(0.71 ±0.02)
Smart Line Modules
7.12 Line connection
10 mm
 / 16 mm
AWG 8 / AWG 6
2
2
a
b
90 +2/-3
15 ±0.5
(3.54+0.08/-0.12)
(0.59 ±0.02)
95 +2/-3
15 ±0.5
(3.74 +0.08/-0.12)
(0.59 ±0.02)
95 +2/-3
18 ±0.5
(3.74+0.08/-0.12)
(0.71 ±0.02)
100 +2/-3
18 ±0.5
(3.94 +0.08/-0.12)
(0.71 ±0.02)