Motor Modules
8.5 Motor Modules 85 A, 132 A and 200 A
Figure 8-77
8.5.6.4

Permissible output current at low frequencies

Technical data
The following diagram shows the permissible output current as a function of the output
frequency when operating with low output frequencies.
Figure 8-78
Output current at low frequencies
For applications with a constant load, e.g. in paper machines, rolling mills etc., the output
current can be reduced as a function of the output frequency. To do this, the pulse frequency
must be set to a frequency less than 4 kHz.
228
Output current as a function of the pulse frequency
Booksize power units