Siemens SIMATIC S7-300 Equipment Manual

Siemens SIMATIC S7-300 Equipment Manual

Industrial ethernet / profinet cp 343-1 lean
Hide thumbs Also See for SIMATIC S7-300:
Table of Contents

Advertisement

Quick Links

CP 343-1 Lean
SIMATIC NET
S7-300 - Industrial Ethernet /
PROFINET
CP 343-1 Lean
Equipment Manual
Manual Part B
01/2023
C79000−G8976−C198−09
Preface
Properties / services
Performance data
Requirements for use
LEDs
Installation, connection,
commissioning, removal
Configuration and
operation
Diagnostics and
maintenance
Technical specifications
Approvals
References
1
2
3
4
5
6
7
8
A
B

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SIMATIC S7-300

  • Page 1 CP 343-1 Lean Preface Properties / services SIMATIC NET Performance data Requirements for use S7-300 - Industrial Ethernet / PROFINET LEDs CP 343-1 Lean Installation, connection, commissioning, removal Equipment Manual Configuration and operation Diagnostics and maintenance Technical specifications Approvals References Manual Part B 01/2023 C79000−G8976−C198−09...
  • Page 2 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 3: Preface

    Preface Legend: ① LEDs ② Under the front panel: PROFINET interface, 2 x 8-pin RJ-45 jack ③ Under the front panel: - Socket for 24 V DC power supply - Slider for setting the ground connector ④ Article number ⑤ Under the front panel: printed text with MAC addresses and firmware version ⑥...
  • Page 4 Preface Firmware version V3.0 Communications processor for SIMATIC S7−300 / C7−300 - conformal coating Note Names • In this document, the term "CP" is used instead of the full product name. • The name STEP 7 is used for the configuration tool instead of the names STEP 7 V5.5 and STEP 7 Professional.
  • Page 5 – Programmed connections and IP configuration – PROFINET IO Current manual edition on the Internet You will also find the current version of this manual on the Internet pages of Siemens Automation Customer Support under the following entry ID: Link: (http://support.automation.siemens.com/WW/view/en/23643456)
  • Page 6 Link: (http://support.automation.siemens.com/WW/view/en/10806067) SIMATIC NET glossary The SIMATIC NET glossary describes terms that may be used in this document. You will find the SIMATIC NET glossary in the Siemens Industry Online Support at the following address: Link: (http://support.automation.siemens.com/WW/view/en/50305045) CP 343-1 Lean...
  • Page 7 Siemens contact. Keep to the local regulations. You will find information on returning the product on the Internet pages of Siemens Industry Online Support: Link: (https://support.industry.siemens.com/cs/ww/en/view/109479891) CP 343-1 Lean Equipment Manual, 01/2023, C79000−G8976−C198−09...
  • Page 8 Preface CP 343-1 Lean Equipment Manual, 01/2023, C79000−G8976−C198−09...
  • Page 9: Table Of Contents

    Table of contents Preface ..............................3 Properties / services ..........................11 Application ........................11 Enhanced functions ......................11 Communication services ....................13 Other services ........................14 The CP as Web server ......................15 Performance data ..........................17 Transmission and reaction times ..................17 Number of possible Ethernet/PROFINET connections ............
  • Page 10 Table of contents Influence of MPI on connections via Industrial Ethernet ............49 PROFINET IO when operating other services at the same time ..........49 Effects of multicast communication on RT communication ..........50 IP configuration ......................... 50 6.8.1 Detection of double IP addressing in the network ............... 50 6.8.2 Obtain IP address vie DHCP: CP STOP on expiry of the lease ..........
  • Page 11: Properties / Services

    Properties / services Application The CP 343- Lean communications processor is intended for operation in a SIMATIC S7-300 or SIMATIC C7 automation system. It allows the connection of the S7-300 to Industrial Ethernet and supports PROFINET IO. To integrate the CP in a linear bus or a ring, to connect a further Ethernet device or to use PROFINET media redundancy, a 2-port ERTEC real-time switch with autocrossing, autonegotiation and autosensing was integrated.
  • Page 12 Enhanced functions of earlier firmware versions and predecessor modules You will find an overview of the earlier firmware versions and predecessor modules in the version history of the Industrial Ethernet CPs on the Internet pages of Siemens Automation Customer Support under the following entry ID: Link: (http://support.automation.siemens.com/WW/view/en/56699406)
  • Page 13: Communication Services

    • PROFINET IO PROFINET IO allows direct access to IO devices over Industrial Ethernet. – PROFINET IO device Integration of the SIMATIC S7-300 automation system via the CP as an intelligent PROFINET IO device (I-device). – Shared device Individual submodules of the CP (IO device) can be assigned up to two PROFINET IO controllers in STEP 7 V5.5.
  • Page 14: Other Services

    Properties / services 1.4 Other services Other services The CP also provides the following additional services: • Media redundancy (MRP) Within an Ethernet network with a ring topology, the CP supports the media redundancy protocol MRP. You can assign the role of MRP client to the CP. •...
  • Page 15: The Cp As Web Server

    Properties / services 1.5 The CP as Web server • Web diagnostics With the aid of Web diagnostics, you can read out the diagnostics data from a station connected via the CP to a PG/PC with a Web browser. This makes it possible to read the diagnostics buffers of the intelligent modules in the rack.
  • Page 16 Properties / services 1.5 The CP as Web server Diagnostics buffer entries When supplied, diagnostics buffer entries shown on diagnostics pages are always in English. This is the case whichever language you have selected to display the Web pages. How to download other language files to the CP and further information about Web diagnostics can be found in the general Part A of this manual.
  • Page 17: Performance Data

    Measured values of transmission and reaction times over Ethernet, PROFIBUS and PROFINET networks for a series of configurations can be found on the Internet at the following address: Link: (http://www.siemens.com/automation/pd) Number of possible Ethernet/PROFINET connections Maximum number of parallel connections...
  • Page 18: Characteristics Of S7 Communication

    Performance data 2.3 Characteristics of S7 communication Also: • Further TCP connections for Web diagnostics • PROFINET IO – As PROFINET IO device: 1 PROFINET connection to a PROFINET IO controller – As shared device: 2 PROFINET connections to 2 PROFINET IO controllers Characteristics of S7 communication Number of connections Table 2- 2...
  • Page 19: Characteristic Data Of The Send/Receive Interface

    S7-300 / C7-300 CPU is decisive for the calculation of the CPU cycle times (OB1) for SEND/RECEIVE connections. Note Measurements of transmission and reaction times in Ethernet, PROFIBUS and PROFINET networks for a series of configurations can be found on the Internet at the following address: Link: (http://support.automation.siemens.com/WW/view/en/25209605) CP 343-1 Lean Equipment Manual, 01/2023, C79000−G8976−C198−09...
  • Page 20: Profinet Io Characteristic Data

    Performance data 2.5 PROFINET IO characteristic data PROFINET IO characteristic data Configuration limits of the CP as an IO device and I-device The CP supports the following maximum configuration if it is configured as a PROFINET IO device and as an I-device: Table 2- 4 Configuration limits of the CP as a PROFINET IO device Characteristic...
  • Page 21: Characteristic Data Of The Integrated Switch

    Measurements of transmission and reaction times in Ethernet, PROFIBUS and PROFINET networks for a series of configurations can be found on the Internet at the following address: Link: (http://support.automation.siemens.com/WW/view/en/25209605) Characteristic data of the integrated switch Learning addresses / deleting addresses (aging time) The switch integrated in the CP (PROFINET interface) reads the source addresses included in the data packets.
  • Page 22 Performance data 2.6 Characteristic data of the integrated switch CP 343-1 Lean Equipment Manual, 01/2023, C79000−G8976−C198−09...
  • Page 23: Requirements For Use

    Requirements for use Operation in control device families The CP can be operated in the following device families: • S7-300 stations with the following CPU types: – Standard – Compact – Modular • C7 compact units in C7 packaging system The following tables show the device environment in which the CP can be operated with the range of functions described here.
  • Page 24 Requirements for use 3.1 Operation in control device families Order number CPU 314 6ES7314-1AE00-0AB0 6ES7314-1AE04-0AB0 6ES7314-1AE84-0AB0 6ES7314-1AF10-0AB0 6ES7314-1AF11-0AB0 6ES7314-1AG13-0AB0 6ES7314-1AG14-0AB0 6AG1314-1AG14-2AY0 6AG1314-1AG14-7AB0 CPU 314 IFM 6ES7314-5AE03-0AB0 6ES7314-5AE10-0AB0 6ES7314-5AE82-0AB0 6ES7314-5AE83-0AB0 CPU 314C-2 DP 6ES7314-6CF00-0AB0 6ES7314-6CF01-0AB0 6ES7314-6CF02-0AB0 6ES7314-6CG03-0AB0 CPU 314C-2 PtP 6ES7314-6BF00-0AB0 6ES7314-6BF01-0AB0 6ES7314-6BF02-0AB0 6ES7314-6BG03-0AB0...
  • Page 25: Project Engineering

    Requirements for use 3.2 Project engineering Order number CPU 317F-2 DP 6ES7317-6FF00-0AB0 6ES7317-6FF03-0AB0 6ES7317-6FF04-0AB0 6AG1317-6FF04-2AB0 CPU 317F-2 PN/DP 6ES7317-2FJ10-0AB0 6ES7317-2FK13-0AB0 6ES7317-2FK14-0AB0 6AG1317-2FK14-2AB0 6AG1317-2FK14-2AY0 CPU 317T-2 DP 6ES7317-6TJ10-0AB0 6ES7317-6TK13-0AB0 CPU 317T-3 PN/DP 6ES7317-7TK10-0AB0 CPU 317TF-3 PN/DP 6ES7317-7UL10-0AB0 CPU 318-2 DP 6ES7318-2AJ00-0AB0 CPU 319-3 PN/DP 6ES7318-3EL00-0AB0 6ES7318-3EL01-0AB0...
  • Page 26 Locating the support package You can install the support package from your local file system if it is already stored there or from the Internet pages of Siemens Automation Customer Support. • STEP 7 V5.5 You will find the support package (HSP) on the Internet at the following address: Link: (http://support.automation.siemens.com/WW/view/en/23183356)
  • Page 27: Program Blocks

    You will find information on the current block versions and the current blocks for download on the Internet under: Link: (https://support.industry.siemens.com/cs/ww/en/ps/15342/dl) With older module types, this recommendation assumes that you are using the latest firmware for the particular module type.
  • Page 28 Requirements for use 3.3 Program blocks CP 343-1 Lean Equipment Manual, 01/2023, C79000−G8976−C198−09...
  • Page 29: Leds

    LEDs LEDs The display on the front panel consists of the following LEDs that indicate the operating mode and communications status. Figure 4-1 LEDs of the CP 343-1 Lean CX10 The LEDs have the following meaning: • SF: Group error •...
  • Page 30 LEDs LEDs for displaying the operating mode The different combinations of the LEDs on the front panel indicate the status: Table 4- 1 LEDs: SF, BF, RUN, STOP SF(red) BF (red) RUN (green) STOP (yellow) CP operating mode • Starting up after power "ON" •...
  • Page 31 LEDs The "MAINT" LED Note When the "MAINT" LED lights up, important error messages and/or diagnostics interrupts have occurred. The CP continues in RUN mode. Check the entries in the diagnostics buffer of the device. LEDs for displaying the CP communications status In addition to the LEDs that signal the CP state, the following LEDs provide information about the status of the CP interface to Industrial Ethernet.
  • Page 32 LEDs CP 343-1 Lean Equipment Manual, 01/2023, C79000−G8976−C198−09...
  • Page 33: Installation, Connection, Commissioning, Removal

    Installation, connection, commissioning, removal Important notes on using the device The following safety notices must be adhered to when setting up and operating the device and during all associated work such as installing, connecting, replacing or removing devices. 5.1.1 Notices on use in hazardous areas WARNING The device may only be operated in an environment with pollution degree 1 or 2 as described in EN/IEC 60664-1, GB/T 16935.1.
  • Page 34: Notes On Use In Hazardous Areas According To Ul Hazloc / Fm

    Installation, connection, commissioning, removal 5.1 Important notes on using the device WARNING Suitable cables at high ambient temperatures in hazardous area Use heat-resistant cables with an ambient temperature ≥ 60 °C; these cables must be rated for an ambient temperature that is at least 20 °C higher. The cable entries used on the housing must comply with the IP degree of protection required by EN IEC 60079-0 / GB 3836.1.
  • Page 35: Installation, Removal And Repairs In Hazardous Areas

    Installation, connection, commissioning, removal 5.2 Installation, removal and repairs in hazardous areas WARNING EXPLOSION HAZARD The equipment is intended to be installed within an ultimate enclosure. The inner service temperature of the enclosure corresponds to the ambient temperature of the module. Use installation wiring connections with admitted maximum operating temperature of at least 30 ºC higher than maximum ambient temperature.
  • Page 36: Installing And Connecting Up

    • Observe the device approvals applicable for your country. WARNING Unauthorized repair of devices in explosion-proof design Risk of explosion in hazardous areas • Repair work may only be performed by personnel authorized by Siemens. Installing and connecting up NOTICE Improper mounting Improper mounting may damage the device or impair its operation.
  • Page 37 Installation, connection, commissioning, removal 5.3 Installing and connecting up WARNING Open equipment The devices are "open equipment" acc. to the standard IEC 61010-2-201 or UL 61010-2-201 / CSA C22.2 No. 61010-2-201. To fulfill requirements for safe operation with regard to mechanical stability, flame retardation, stability, and protection against contact, the following alternative types of installation are specified: •...
  • Page 38 Installation, connection, commissioning, removal 5.3 Installing and connecting up Legend: Attachment to Industrial Ethernet (PROFINET interface): 2 x 8pin RJ45 jack Connecting the power supply Slider for setting the chassis ground connection Figure 5-1 Connectors of the CP Ground/chassis ground concept Note Note the instructions regarding the grounding and chassis ground concept in the SIMATIC S7 installation guides;...
  • Page 39 Installation, connection, commissioning, removal 5.3 Installing and connecting up Installing and connecting up NOTICE Ensuring ventilation During installation, make sure that the upper and lower ventilation slits of the module are not obstructed and good ventilation is possible. 1. Install the CP on the S7 standard rail. Slots 4 to 11 are permitted for the CP in racks 0 to 3 (connected by IM 360/361).
  • Page 40 Installation, connection, commissioning, removal 5.3 Installing and connecting up Diagnostics Use the diagnostic functions during commissioning and to analyze problems. The following options are available: • The LED displays on the CP • Hardware diagnostics and troubleshooting with STEP 7 •...
  • Page 41 Installation, connection, commissioning, removal 5.3 Installing and connecting up Connecting interface X1 to Industrial Ethernet 1. Connect the CP to Industrial Ethernet via one of the RJ45 jacks. 2. Where necessary, connect another component to the remaining free RJ45 jack. Note Autocrossing mechanism - effects on the connectors For small local area networks or for attaching several Ethernet devices, a 2port switch has...
  • Page 42: Disassembly

    Installation, connection, commissioning, removal 5.4 Disassembly Disassembly WARNING Improper disassembly Improper disassembly may result in a risk of explosion in hazardous areas. For proper disassembly, observe the following: • Before starting work, ensure that the electricity is switched off. • Secure remaining connections so that no damage can occur as a result of disassembly if the system is accidentally started up.
  • Page 43: Configuration And Operation

    • Do not connect the device directly to the Internet. Operate the device within a protected network area. • Check the Siemens website regularly for the latest information. – You can find information on Industrial Security here: Link: (http://www.siemens.com/industrialsecurity) –...
  • Page 44 Configuration and operation 6.1 Security recommendations Security functions of the product Use the options for security settings in the configuration of the product. These includes among others: • Protection levels Configure access to the CPU under "Protection". • Leave access to the Web server of the CPU (CPU configuration) and to the Web server of the CP disabled.
  • Page 45 Configuration and operation 6.1 Security recommendations • Default of the port – Open The port is open at the start of the configuration. – Closed The port is closed at the start of the configuration. • Port status – Open The port is always open and cannot be closed.
  • Page 46: Project Engineering

    Configuration and operation 6.2 Project engineering Project engineering Project engineering To set up the CP for communication services, read the information on configuring in the sections Project engineering (Page 25) and Replacing a module without a programming device (Page 63). For detailed information on configuration, refer to Part A of this manual, see References /1/ (Page 73).
  • Page 47: Network Settings

    Configuration and operation 6.4 Network settings Network settings The configuration of the network settings "Transmission medium / Duplex" is made in the properties dialog of the port of the interface in the "Options" tab. Row "X1P1": Properties of port 1 of the PROFINET interface Row "X1P2": Properties of port 2 of the PROFINET interface Automatic setting or individual network settings As default, the CP is configured for automatic detection (autosensing / autonegotiation /...
  • Page 48 Configuration and operation 6.4 Network settings Further notes: • Autocrossover If you disable the "Automatic setting" option, autocrossing is disabled; which cable you then use depends on the integration of the CP (network component or end device). • 10/100 Mbps network components without "autonegotiation" If you use 10/100 Mbps network components that do not support "Autonegotiation", it is possible that you will have to set the mode manually in the CP configuration in STEP 7.
  • Page 49: Influence Of Mpi On Connections Via Industrial Ethernet

    Configuration and operation 6.5 Influence of MPI on connections via Industrial Ethernet Influence of MPI on connections via Industrial Ethernet Adding/removing MPI nodes If a station on the MPI bus is added or removed, for example because a service PG has been connected or disconnected, it is possible that active communication connections on the communications bus are aborted.
  • Page 50: Effects Of Multicast Communication On Rt Communication

    ("switch depth"), the update time and the MC/BC frame lengths. You will find further information about the influencing factors as well as possible solutions in: Link: (http://support.automation.siemens.com/WW/view/en/29104898) IP configuration 6.8.1 Detection of double IP addressing in the network To save you timeconsuming troubleshooting in the network, the CP detects double addressing in the network.
  • Page 51: Obtain Ip Address Vie Dhcp: Cp Stop On Expiry Of The Lease

    Configuration and operation 6.9 Media redundancy 6.8.2 Obtain IP address vie DHCP: CP STOP on expiry of the lease If you have configured “Obtain IP address from a DHCP server", when the CP starts up, it is assigned a valid IP address by the DHCP server for a restricted time (period of the lease). Note STOP on expiry of the lease The CP changes to STOP and loses the previously assigned IP address if the DHCP server does...
  • Page 52: Snmp Agent

    SNMP client you are using (example of an SNMP client: SNMP OPC server from SIMATIC NET). For more information on SNMP, refer to the SNMP manual: Link: (https://support.industry.siemens.com/cs/ww/en/ps/15392/man) Supported MIBs The CP supports the following groups of MIB objects of the standard MIB II according to RFC1213: •...
  • Page 53 Configuration and operation 6.11 SNMP agent Exceptions / restrictions: • Write access is permitted only for the following MIB objects of the system group: – sysContact – sysLocation – sysName A set sysName is sent as the host name using DHCP option 12 to the DHCP server to register with a DNS server.
  • Page 54: Possible Security Gaps On Standard It Interfaces: Preventing Unauthorized Access

    If you have questions on the use of firewall systems and IT security, please contact your local Siemens office or representative. You will find the address in the SIMATIC catalog IK PI or on the Internet at the following address: (http://www.automation.siemens.com/partner/guisearch.asp)
  • Page 55: Programmed Communication Connections

    Configuration and operation 6.13 Programmed communication connections 6.13 Programmed communication connections 6.13.1 Programmed communication connections with FB55 IP_CONFIG Downloading the configuration using FB55 IP_CONFIG IP_CONFIG allows programcontrolled transfer of the configuration data. Note If the CP is in PG STOP mode and the configuration is downloaded using IP_CONFIG, the CP then changes automatically to RUN.
  • Page 56 Configuration and operation 6.14 Permitted length of ICMP packets CP 343-1 Lean Equipment Manual, 01/2023, C79000−G8976−C198−09...
  • Page 57: Diagnostics And Maintenance

    Diagnostics and maintenance CAUTION Hot surfaces Risk of burns during maintenance work on parts with a surface temperature above 70 °C (158 °F). • Take appropriate protective measures, for example, wear protective gloves. • Once maintenance work is complete, restore the touch protection measures. WARNING Cleaning the housing •...
  • Page 58: Memory Reset / Reset To Factory Defaults

    Diagnostics and maintenance 7.2 Memory reset / reset to factory defaults • STEP 7 V5.5 – Hardware diagnostics and troubleshooting – Communication diagnostics with special diagnostics • STEP 7 Professional In the "Diagnostics" tab in the Inspector window, you will see the following information: –...
  • Page 59 Diagnostics and maintenance 7.2 Memory reset / reset to factory defaults Available functions The CP has a twolevel function available for resetting memory: • Memory reset Following this memory reset, the CP retains the preset MAC address and the retentive parameters.
  • Page 60: Loading New Firmware

    Diagnostics and maintenance 7.3 Loading new firmware Loading new firmware Options for a firmware update The following alternative methods can be used to download new firmware to a SIMATIC NET • Using the firmware loader supplied with STEP 7 Requirement for downloading: –...
  • Page 61: Replacing A Module

    Diagnostics and maintenance 7.4 Replacing a module Replacing a module Note Recommendation to reset address data if the use of the CP is changed The following data is stored permanently on the CP: • IP parameters when using DHCP If the CP has already been operated in your plant and you want to use it at a different location in the plant, it starts up with the permanently configured parameters.
  • Page 62: Module Replacement / Upgrading

    You should always use the latest block versions for new user programs. You will find information on the current block versions and the current blocks for downloading on the Internet under: Link: (https://support.industry.siemens.com/cs/ww/en/ps/15342/dl) CP 343-1 Lean Equipment Manual, 01/2023, C79000−G8976−C198−09...
  • Page 63: Replacing A Module Without A Programming Device

    Diagnostics and maintenance 7.4 Replacing a module Module replacement Please follow the procedure below when replacing an older module with the module described here: Table 7- 1 Replacing an older module Originally configured module Configuration procedure 6GK7 343-1CX00-0XE0 Case a: Configuration unchanged / module replacement If you have no requirements beyond what you had with the previous CP (for example PROFINET IO mode), you do not need to make changes in the configuration.
  • Page 64 Diagnostics and maintenance 7.4 Replacing a module Module replacement: Special feature of IP address assignment from a DHCP server During configuration of the CP you can specify the IP configuration in the properties dialog; one option is to obtain the IP address from a DHCP server. Note When replacing modules, please remember that the factoryset MAC address of the new module is different from the previous module.
  • Page 65: Technical Specifications

    Technical specifications Table 8- 1 Technical specifications Technical specifications Attachment to Industrial Ethernet Number 1 x PROFINET interface with 2port switch Execution Connector 2 x RJ-45 jacks Transmission rate 10 / 100 Mbps When working with PROFINET IO and cyclic transfer, the transmission speed of 100 Mbps full duplex is mandatory.
  • Page 66 Technical specifications In addition to this, all the information in the "SIMATIC S7-300 Automation System Module Data" see /12/ (Page 76) in the section "General Technical Specifications" on the topics listed below applies to the CP: • Electromagnetic compatibility • Transportation/storage conditions •...
  • Page 67: Approvals

    Approvals for shipbuilding are not printed on the device type plate. Current approvals on the Internet You will find the current approvals for the product on the Internet pages of Siemens Industry Online Support at the following link: (https://support.industry.siemens.com/cs/ww/en/ps/15345/cert)
  • Page 68 Directive of the European Parliament and of the Council of 8 June 2011 on the restriction of the use of certain hazardous substances in electrical and electronic equipment UK Declaration of Conformity Importer UK: Siemens plc Sir William Siemens House Princess Road Manchester M20 2UR The product meets the requirements of the following directives: •...
  • Page 69 • EN IEC 60079-0 - Explosive atmospheres - Part 0: Equipment - General requirements • EN 60079-7 - Explosive Atmospheres - Part 7: Equipment protection by increased safety 'e' Importer UK: Siemens plc (see above) CP 343-1 Lean Equipment Manual, 01/2023, C79000−G8976−C198−09...
  • Page 70 Approvals Classification: Ex na IIC T4 Gc The product meets the requirements of the following standards: • GB 3836.1 Explosive atmospheres - Part 0: Equipment - General requirements • GB 3836.3 Explosive atmospheres - Part 3: Equipment protection by increased safety "e" •...
  • Page 71 Approvals cULus Hazardous (Classified) Locations Underwriters Laboratories Inc. cULus Listed 7RA9 IND. CONT. EQ. FOR HAZ. LOC.: • UL 508 (Industrial Control Equipment) • UL 1604 (Hazardous Location) • CSA C22.2 No. 142 (Pocess Control Equipment) • CSA C22.2 No. 213 (Hazardous Location) APPROVED for Use in: •...
  • Page 72 Approvals CP 343-1 Lean Equipment Manual, 01/2023, C79000−G8976−C198−09...
  • Page 73: References

    • Documentation in the STEP 7 V5 installation Manuals that are included in the online documentation of the STEP 7 installation on your PG/PC can be found in the start menu ("Start" > "All Programs" > "Siemens Automation" > "Documentation").
  • Page 74 For configuration with STEP 7 / NCM S7 SIMATIC NET Version history / current downloads for the SIMATIC NET S7 CPs History document Siemens AG (SIMATIC NET Manual Collection) On the Internet under following entry ID: Link: (https://support.industry.siemens.com/cs/ww/en/ps/15342/dl) For configuration with STEP 7 / NCM S7...
  • Page 75 On programming SIMATIC NET Program blocks for SIMATIC NET S7 CPs Version history, reference document Siemens AG Entry ID: Link: (https://support.industry.siemens.com/cs/ww/en/ps/15342/dl) SIMATIC Programming with STEP 7 Siemens AG (Part of the STEP 7 documentation package STEP 7 Basic Knowledge) (Part of the online documentation in STEP 7) Link: (http://support.automation.siemens.com/WW/view/de/18652056)
  • Page 76 On installing and commissioning the CP /10/ SIMATIC NET Program blocks for SIMATIC NET S7 CPs Programming Manual Siemens AG Link: (https://support.industry.siemens.com/cs/ww/en/view/62543517) /11/ Automatisieren mit STEP 7 in AWL und SCL (ISBN: 978-3-89578-280-0) / Automating with STEP 7 in STL and SCL (ISBN: 978-3-89578-295-4)
  • Page 77 References On setting up and operating an Industrial Ethernet network /14/ SIMATIC From PROFIBUS DP to PROFINET IO Programming manual Siemens AG (SIMATIC NET Manual Collection) On setting up and operating an Industrial Ethernet network /15/ SIMATIC NET Industrial Ethernet...
  • Page 78 References Other topics Siemens AG Order number 6ES7 810-4CA08-8AW0 (part of the online documentation in STEP 7) Other topics /19/ Ethernet, IEEE 802.3 (ISO 8802-3) (http://www.ieee.org) /20/ RFC 1006 (ISO Transport Service on top of the TCP Version: 3) Request For Comment (http://www.ietf.org)
  • Page 79: Index

    Index Abbreviation "CX", 11 Addressing, 39 Ping, 55 PROFIenergy, 11 Programmed connections and IP configuration, 5 Connection and system diagnostics, 5 CX (abbreviation), 11 Recycling, 7 Diagnostics, 40 Disposal, 7 SIMATIC NET glossary, 6 Documentation, 5 STEP 7, 4 Download, 39 STEP 7 version, 11, 25 Downloads, 5 Version history, 5...

Table of Contents