Connectable Cable Cross-Sections; Mounting The Dc Link Adapter - Siemens SINAMICS S220 Equipment Manual

Booksize power units
Hide thumbs Also See for SINAMICS S220:
Table of Contents

Advertisement

11.4.5.3

Connectable cable cross-sections

Description
Table 11-10
Feature
Cable cross-sections
Stripped length
11.4.5.4

Mounting the DC link adapter

Requirement
You can use the DC link adapter to supply one or several components. If you use the DC link
adapter to supply several components that are mounted directly adjacent to one another, then
the installation must meet the following requirements:
• The component line-up must be established to the left.
• The DC link adapter must be mounted onto the component at the far right.
Required tools:
• Slotted screwdriver 1.0 x 5.5 mm to release the protective flap
• Torx screwdriver TX 20
• Torx screwdriver TX 10 to fasten the DC link adapter
• Pliers for breaking out the cutout
Booksize power units
Equipment Manual, 09/2023, A5E53307519B AA
Conductor cross-sections of the cable for the DC link adapter 200 A
Cable cross-sections
Single core connection:
35 ... 120 mm
 (AWG 4 ...4/0)
2
27 mm
Accessories
11.4 DC link adapter
295