8.3.10.7

Connecting the cable shield

Overview
The motor connection cable shield is attached to the shield connection plate of the Motor
Module using the shield connection clamp supplied.
Requirement
Note
Ensuring twist protection
For the shield connection clamp, twist protection of the pressure plate is only ensured when
completely swung back (state when delivered). After the shield connection clamp has been
fitted in the shield connection plate, the shield connection plate prevents twisting.
The connection plug and/or the 2 connection plugs for a Double Motor Module are inserted
in connection sockets X1 and/or X2 at the Motor Module.
Procedure
Figure 8-31
Proceed as follows to fix the motor connection cable or the motor connection cables:
1. Route the cable or both cables through the shield connection plate.
2. Hook the shield connection clamp into the shield connection plate.
3. Fix the cable using the pressure plate. To do this, tighten the knurled screws. Tightening
torque: 0.8 Nm (7.08 lbf in)
184
Knurled screws
Slots to hook the shield connection clamp into the shield connection plate
Pressure plates
Shield connection - example for a Double Motor Module with two pressure plates
Booksize power units
Equipment Manual, 09/2023, A5E53307519B AA