Connecting The Cable Shield - Siemens SINAMICS S220 Equipment Manual

Booksize power units
Hide thumbs Also See for SINAMICS S220:
Table of Contents

Advertisement

Motor Modules
8.5 Motor Modules 85 A, 132 A and 200 A
Example
Figure 8-85
8.5.12.6

Connecting the cable shield

Overview
You can fasten the shield of the motor connection cable to the shield connection plate of the
Motor Module using a hose clamp or a shield connection clamp.
Requirement
The following requirements must be satisfied:
• The motor connection cable is connected at the motor connection block.
• The shield connection plate is mounted.
• Use a suitable hose clamp or shield connection clamp.
Shield connection clamp
Phoenix SK 14
Phoenix SK 28
Phoenix SK 35
240
Example of installed reduction collars
Use
For shielded single cores with a conductor diameter of up to
14 mm (0.55 inch)
For shielded single cores with a conductor diameter of up to
28 mm (1.1 inch)
For shielded cables with a cable diameter of up to 35 mm
(1.38 inch)
Article number
8WH9130-0MA00
8WH9130-0NA00
8WH9130-0PA00
Booksize power units
Equipment Manual, 09/2023, A5E53307519B AA