Required tools:
• Hexagon size 10 or Torx screwdriver TX 25
Procedure
Proceed as follows to connect the protective conductor to the protective conductor connection
of the Motor Module:
1. Prepare the cable with an appropriate ring/tubular cable lug.
2. Open the motor connection block cover to connect the motor connection cable.
3. Connect the protective conductor to the component using the screw for the protective
conductor connection.
4. Tighten the screw. Hexagon size 10 or Torx screwdriver TX 25. Tightening torque: 6 Nm (53.1
lbf in)
Figure 8-48
8.4.11
Connecting the motor
8.4.11.1
Connectable cable cross-sections
Description
Table 8-25
Output current [A]
45 A and 60 A
Booksize power units
Equipment Manual, 09/2023, A5E53307519B AA
Position of the protective conductor connection at Motor Modules 45 A and 60 A
Conductor cross-section of the motor cable for Motor Modules 45 A and 60 A
Cable cross-sections
Single core connection:
6 ... 50 mm
2
(AWG 10 ... 1)
Two-wire connection:
4 ... 25 mm
(AWG 12 ... 4)
2
Motor Modules
8.4 Motor Modules 45 A and 60 A
203