Connecting the motor

8.3.10.1

Connectable cable cross-sections

Description
Table 8-12
Conductor cross-sections and tightening torques
Output current
3 ... 30 A
Plug with screw terminal
(6SL3162-2MA00-0AC0)
2 x 3 A ... 2 x 18 A
Plug with push-in connection
(6SL3162-2MB00-0AC0)
8.3.10.2

Preparing the motor connection cable

Overview
Motors are connected to a Motor Module using a motor connection cable with a connection
plug. We recommend that you use a completely prefabricated MOTION-CONNECT power cable.
If you are using a power cable or a MOTION-CONNECT power cable that has not yet been
completely prefabricated, then you must first fabricate the motor connection cable.
Requirement
NOTICE
Adherence to core and stripped lengths
If the specified core and stripped lengths are not complied with, single cores can be damaged
or shield contact prevented.
• Comply with the specified core and stripped lengths.
It is not possible to self-assemble motor connection cables having a core cross-section of
10 mm
Booksize power units
Equipment Manual, 09/2023, A5E53307519B AA
Motor connection
. In this case, use pre-assembled MOTION-CONNECT power cables.
2
8.3 Motor Modules 3 ... 30 A and 2x3 ... 2x18 A
Cable cross-sections
Finely stranded connection with:
0.75 ... 6 mm
(AWG 19 ... 10)
2
Motor Modules
Tightening torque
0.5 - 0.6 Nm (4.4 lbf in)
-