Siemens SINAMICS S220 Equipment Manual page 93

Booksize power units
Hide thumbs Also See for SINAMICS S220:
Table of Contents

Advertisement

Required tools:
• Slotted screwdriver 1.0 x 5.5 mm to release the protective flap
• Torx screwdriver TX 10 to fasten the 24 V terminal adapter
• Slotted screwdriver 1.0 x 4.0 mm
• Pliers for breaking out the cutout
Procedure
Figure 5-7
Proceed as follows to mount the 24 V terminal adapter:
1. Release and open the protective flap of the component. Slotted screwdriver 1.0 x 5.5 mm
2. Clip the 24 V terminal adapter on to the 24 V busbars.
3. Firmly attached the 24 V terminal adapter using the screw provided. Torx screwdriver TX 10.
Tightening torque: 0.8 Nm (7 lbf in)
4. Using pliers, break out the cutout in the protective flap.
5. Close the protective flap until you hear it snap into place.
6. Fasten the 24 V DC supply cables to the 24 V terminal adapter. Slotted screwdriver
1.0 x 4.0 mm. Tightening torque: 1.2 ... 1.5 Nm (10.6 ... 13.3 lbf in)
Booksize power units
Equipment Manual, 09/2023, A5E53307519B AA
24 V terminal adapter
Screw for fixing
Mounting the 24 V terminal adapter
Mounting
5.4 24 V terminal adapter
91