Line filters can optionally be used for Smart Line Modules in conjunction with the associated line
reactors. In conjunction with line reactors and a consequential EMC-compliant system design,
line filters limit the conducted electromagnetic emissions generated by the Line Modules to the
limit values according to IEC 61800-3. They are mainly effective in the frequency range from
9 kHz to 30 MHz; this is the range relevant to ensure compliance with the appropriate standard.
Table 6-2
Line filter
16 kW
24 kW
6.5.2

Safety information

Electric shock due to residual charges in power components
As a result of the capacitors, a hazardous voltage is present for up to 5 minutes after the power
supply has been switched off.
Contact with live parts can result in death or serious injury.
• Wait for 5 minutes before you check that the unit really is in a no-voltage condition and start
High leakage currents when the protective conductor in the line supply cable is
interrupted
The drive components conduct a high leakage current via the protective conductor. Touching
conductive parts when the protective conductor is interrupted can result in death or serious
injury.
• Adhere to the requirements for the dimensioning of the protective conductor set out in this
Burns due to high surface temperatures
The surface of the components can reach high temperatures during operation. You can get
seriously burnt when touching the surface.
• Do not touch the component.
Booksize power units
Equipment Manual, 09/2023, A5E53307519B AA
Line filters for Smart Line Modules
WARNING
work.
WARNING
Equipment Manual.
CAUTION
Line-side power components
Article number
6SL5100-0HE21-6DD0
6SL5100-0HE22-4DD0
6.5 Line filter