4.2.3

Dynamic Drive Control

Select the motor standard.
● KW 50HZ: IEC
● HP 60HZ: NEMA
● KW 60HZ: IEC 60 Hz
Set the inverter supply voltage.
Select the motor type. Depending on the particular inverter, it is possible that the BOP-2
does not list all of the following motor types.
● INDUCT: Third-party induction motor
● SYNC: Third-party synchronous motor
● RELUCT: Third-party reluctance motor
● 1L... IND: 1LE1, 1LG6, 1LA7, 1LA9 induction motors
● 1LE1 IND 100: 1LE1 . 9 with motor code on the rating plate
● 1PC1 IND: 1PC1 with motor code on the rating plate
● 1PH8 IND: Induction motor
● 1FP1: Reluctance motor
● 1F... SYN: 1FG1, 1FK7 synchronous motor, without encoder
If you have selected a motor type > 100, then you must enter the motor code:
With the correct motor code, the inverter assigns the motor data the following values.
If you do not know the motor code, then you must set the motor code = 0, and enter the
motor data from p0304 and onwards from the rating plate.
87 Hz motor operation The BOP-2 only displays this step if you previously selected IEC as
the motor standard (EUR/USA, P100 = KW 50HZ).
Rated motor voltage
Rated motor current
Rated motor power
Rated motor frequency
Rated motor speed
SINAMICS G120C, FSD ... FSF inverters
Compact Operating Instructions, 11/2016, FW V4.7 SP6, A5E39339884B AA
4.2 Commissioning with BOP-2 operator panel
Commissioning
47