HPE ProLiant DL365 Gen11 Maintenance And Service Manual page 49

Table of Contents

Advertisement

Procedure
Procedure
1. Extend the server from the rack .
2. Remove the access panel .
3. Remove the fan blank.
Results
Results
To replace the component, reverse the removal procedure.
Removing and replacing a fan
Removing and replacing a fan
About this task
About this task
CAUTION: Do not operate the server for long periods with the access panel open or removed. Operating the server in this
CAUTION:
manner results in improper airflow and improper cooling that can lead to thermal damage.
IMPORTANT: For optimum cooling, install fans in all primary fan locations.
IMPORTANT:
Procedure
Procedure
1. Extend the server from the rack.
2. Remove the access panel .
3. Remove the fan.
IMPORTANT: When a hot-plug fan is removed, the other fans in the server will increase speed to compensate.
IMPORTANT:
CAUTION: To avoid server shutdown, a fan must be replaced within 60 seconds of being removed.
CAUTION:
HPE ProLiant DL365 Gen11 Server Maintenance and Service Guide
49