3-14
Wiring System, Axis, and Shunt Modules, and Motors (for all systems)
Wire:
24V Logic
360/480V AC
Input Power
Input Power
Neutral
PE Ground
External Shunt
Resistor
Publication 1394-5.0 — May 2000
Terminal Block Locations for 5 and 10 kW System Module
(Series A and B)
The 5 and 10 kW system module (Series A and B) components use
IEC terminals for power connections. You will wire the system and
axis modules using the power terminal block conveniently located at
the bottom front of the system and axis modules. The maximum wire
size allowed in the terminal blocks is 3.3 mm
access to the input power terminals, open the system module door and
look in the lower right corner. Refer to Figure 3.10 for terminal block
details.
!
Figure 3.10
Terminal Block for a 5 or 10 kW System Module (Series A and B)
Description:
A user-supplied 24V AC rms or 24V DC power source. Refer to
Appendix A for 24V input power specifications.
360/480V AC, three-phase power input Refer to Appendix A for
system specifications for rated AC input voltage, tolerance, and
source impedance.
Three-phase input neutral (present only on grounded power
configurations).
The 1394's ground connection to the bonded system ground
bar on the subpanel.
Optional 1400W external shunt resistor used to dissipate
excess regenerative energy from the system module.
Note:
Refer to Appendices A and B for information about three-phase
input fusing and circuit breaker information as related to the
power input. Refer to the section Connecting Your External
Shunt Resistor for information about wiring the optional shunt
resistor to the 5 and 10 kW system modules.
ATTENTION: To avoid personal injury and/or
equipment damage ensure installation complies with
specifications regarding wire types, conductor sizes,
branch circuit protection, and disconnect devices. The
National Electrical Code (NEC) and local codes
outline provisions for safely installing electrical
equipment.
Connects to terminal(s): Required (Y/N):
W1 and W2
U, V, and W
System ground bar
PE
DC+ and COL
2
(12 AWG). To gain
Y
Y
N
Y
N