8 Other Functions
Parameter No.
3005Hex-4DHex
3005Hex-15Hex/
3005Hex-1CHex
Main Circuit
DC Voltage
"U-EDC"
8-8-22

AX Terminal Function (AX)

This function is used to control the electromagnetic contactor (MC) at the inverter input side in associ-
ation with the RUN command. It turns ON when the RUN command is input. When the stop command
is input, this function turns OFF after the inverter undergoes a deceleration stop. This function turns
OFF momentarily when the free run command is input and an alarm is generated. "AX" can be select-
ed at a capacity of 18.5kW or more of auxiliary power supply.
Connect the power supply directly between R0 and T0.
Parameter No.
3005Hex-15Hex/
3005Hex-1CHex
8-94
Function name
Main Circuit DC Voltage Low-
voltage Detection Level
Output Terminal [DO1] Func-
tion Selection/Output Terminal
[ROA, ROB] Function Selec-
tion
Function name
Output Terminal [DO1] Func-
tion Selection/Output Terminal
[ROA, ROB] Function Selec-
tion
MC
Power supply
MC
"FW"
Data
200 to 400V (200Vseries)
400 to 800V (400Vseries)
77: U-EDC (Low DC link bus
voltage detection)
Main Circuit DC Voltage Low-voltage
Detection Level (3005Hex-4DHex)
Data
15: AX (Switch MC on the in-
put power lines)
L1/R to L3/T
U, V, W
R0, T0
DO1 ("AX")
FW
3G3M1
M1 Series EtherCAT Type User's Manual (I670)
Default data
Unit
235
V
-
-
Default data
Unit
-
-
M
Motor