When using vector control without speed sensor, do not use restarting from the pull-in frequen-
cy (Starting Frequency Selection at Frequency Pull-in Restart (301FHex-35Hex)). If you select
starting from pull-in frequency, normal start may not be performed, or the device may be
damaged.
Use the retry function to recover from overvoltage or overcurrent.
(3008Hex-05Hex: Retry Count at Trip, 3008Hex-06Hex: Retry Standby Time at Trip)
As for the starting method, the settings in E139 is applied.
Output frequency
(motor rotation speed)
8-4-4

Unattended Start Protection (USP Terminal)

• Use this function to have the inverter trip if the power supply is turned ON with the RUN command
ON in the inverter.
• When the RUN command is ON and multifunction input "USP" is ON when the power is ON, a run
operation error (alarm code: 24, sub code: 30) is generated
• When the run operation error is reset with the RUN command still ON, operation is started regard-
less of the ON/OFF setting of "USP." (Example 1)
• If the RUN command turns ON after the power supply is turned ON, the inverter operates normally.
(Example 2)
• Allocate "186: USP (Unattended start protection)" to Input Terminal [DI1] to [DI7] Function Selection
(3005Hex-02Hex to 3005Hex-06Hex, 3005Hex-63Hex, 3005Hex-64Hex).
• Power recovery restart prevention based on USP input is enabled only for a RUN command from
the terminal block.
Parameter No.
3005Hex-02Hex to
3005Hex-06Hex,
3005Hex-63Hex,
3005Hex-64Hex
The operation of the unattended start protection is shown below.
M1 Series EtherCAT Type User's Manual (I670)
Overvoltage/overcurrent detection
Auto-resetting
"TRY"
Function name
Input Terminal [DI1] to [DI7]
Function Selection
Pull-in*
3008Hex-06Hex
*Example of the set frequency (301FHex-35Hex = 2)
Data
186: USP (Unattended
start protection)
8 Other Functions
Auto search
Restart from
starting frequency
Default da-
Unit
ta
-
8
-
8-51