Appendices
Event name
Overvoltage Protection (During Deceleration)
Meaning
Overvoltage occurred during deceleration.
Source
EtherCAT Master Function Mod-
ule
Error attrib-
Level
utes
Effects
User program
Indicators
EtherCAT NET RUN
---
System-de-
Variable
fined varia-
None
bles
Cause and
Assumed cause
correction
(1) The inverter's power supply
voltage exceeds the specified
range.
(2) A surge current occurred the
input power supply.
A-232
Source details Slave
Minor fault
Recovery
Continues.
Operation
EtherCAT NET ERR
---
Data type
None
Correction
Measure the input voltage.
→ Decrease the power supply
voltage to within the specified
range.
→ If the power supply voltage is
within the specified range, there
is a possibility of an inverter fail-
ure.
When the phase advance capac-
itor is turned ON or OFF in the
same power supply system, or
when the thyristor converter op-
erates, the input voltage may
transiently become abnormally
high (i.e., surge).
→ Install a DC reactor.
Event code
087D0000 hex
Detection tim-
ing
Error reset
Log category
Motor stops.
EtherCAT LINK/ACT
---
Name
None
Prevention
Input the correct voltage.
Install a DC reactor.
M1 Series EtherCAT Type User's Manual (I670)