Input Terminal Response Time; Multi-Function Output Terminal Selection - Omron 3G3MX2 User Manual

Sysdrive mx2 series multi-function compact inverter
Hide thumbs Also See for 3G3MX2:
Table of Contents

Advertisement

Input Terminal Response Time

A sampling time can be set individually for each of multi-function input terminals S1 to S7/EB.
Helps remove chattering and other noises. If the terminal input becomes unstable because of
chattering, etc. increase the data value.
The larger the data value is, the slower the response time. A setting range of 0 to 200 is
available, which corresponds to approx. 2 to 400 ms.
Parameter
No.
C160 to C166
Note. The response time is ignored upon power ON or reset. For example, if the power is turned on while
the FW terminal is still ON, operation resumes immediately regardless of the set value of response
time.

Multi-function Output Terminal Selection

The following functions can be allocated to Multi-function Output Terminal P1/EDM to P2
Selections (C021 to C022) and Multi-function Relay Output (MA, MB) Function Selection
(C026). Multi-function output terminals P1/EDM, P2 are open-collector output, while multi-
function relay output terminal MA, MB are relay output.
NO or NC contact can be selected individually for each output terminal using C031, C032 or
C036.
Data
00
RUN: During RUN
01
FA1: Constant speed reached
02
FA2: Set frequency min. reached
03
OL: Overload warning
04
OD: PID excessive deviation
05
AL: Alarm output
06
FA3: Set frequency only
07
OTQ: Overtorque/Undertorque
UV: Signal during undervoltage
09
10
TRQ: During torque limit
11
RNT: RUN time over
12
ONT: Power on time over
13
THM: Thermal warning
19
BRK: Brake release
20
BER: Brake error
21
ZS: 0Hz
22
DSE: Excessive speed deviation
23
POK: Position ready
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
Function name
Input Terminal
0. to 200. (× 2 ms)
Response Time
Approx. 2 to 400 ms
Description
5-3 Input/Output Terminals
Data
Reference item
Signal During RUN
Frequency Arrival Signal
Overload Limit/Overload Warning
PID Function
Alarm Signal
Frequency Arrival Signal
Overtorque/undertorque
Restart Upon Momentary Power Interruption/
Undervoltage, Overvoltage/Overcurrent
Torque Limit Function
RUN/Power ON Time Exceeded
Electronic Thermal Function
Brake Control Function
0-Hz Signal (ZS)
Simple Position Control Mode
Default
Unit
setting
1.
ms
Page
5-121
5-122
5-115
5-73
5-119
5-122
5-152
5-96
5-153
5-124
5-113
5-142
5-125
5-160
5-32
5