Installation Conditions
Keep the inverter clear of heating elements such as a braking resistor or reactor.
If the inverter is installed in a control panel, take into consideration dimensions and ventilation to keep
the ambient temperature within the range of the specifications.
To allow heat dispersion from inside the inverter (approx. 150°C or lower), provide the clearance
specified in the figure below during installation.
 Standard installation
10mm
100 mm
min.
min.
 Side-by-side installation
10 mm min.
Ambient Temperature Control
To ensure reliable operation, use the inverter in an environment subject to minimal temperature rise as
much as possible.
If you install a ventilation fan in a control panel where several inverters are installed, be careful about
the layout of the inverters and the air intake and ventilation apertures.
Remember that poor air circulation around inverters causes an internal temperature rise, which may
inversely affect the internal components of the inverters.
M1 Series EtherCAT Type User's Manual (I670)
100 mm
min.
Flow of air
Inverter
10mm
min.
4 mm min.
4 mm min.
Provide a sufficient
clearance from upper
and lower wiring
ducts, etc. to prevent
the flow of cooling air
from being blocked.
Wall
100 mm min.
Flow of air
Inverter
Wall
100 mm min.
* Ensure a clearance of 4 mm or more between inverters.
2 Design
Provide a sufficient
clearance from upper
and lower wiring
ducts, etc. to prevent
the flow of cooling air
from being blocked.
2-3
2