Power
Standard applicable
supply
motor (kW)
line
Three-
18.5
phase 400
V
22
30
37
Single-
0.1
phase 200
0.2
V
0.4
0.55
0.75
1.1
1.5
2.2
3
3.7
• Use a molded case circuit breaker (MCCB), residual current device (RCD) or earth leakage
circuit breaker (ELCB), and magnetic contactor (MC) that are compliance with EN or IEC
Standards.
• When using a residual current device (RCD) or earth leakage circuit breaker (ELCB) as
protection against electric shock through direct or indirect contact with the power line or
node, be sure to install a RCD or ELCB of type B (DC capable) model on the input side
(primary side) of the inverter.
M1 Series EtherCAT Type User's Manual (I670)
Inverter model
3G3M1-A4110-ECT
ND
3G3M1-A4150-ECT
HND
HD
3G3M1-A4185-ECT
HHD
3G3M1-A4150-ECT
ND
3G3M1-A4185-ECT
HND
HD
3G3M1-A4220-ECT
HHD
3G3M1-A4185-ECT
ND
3G3M1-A4220-ECT
HND
HD
ND
3G3M1-AB001-ECT
HHD
HND
3G3M1-AB002-ECT
HHD
HND
3G3M1-AB004-ECT
HHD
HND
3G3M1-AB007-ECT
HHD
HND
3G3M1-AB015-ECT
HHD
HND
3G3M1-AB022-ECT
HHD
HND
3G3M1-AB037-ECT
HHD
MCCB
Disconnect
or
MC
Cutter
RCD/ELCB, etc,
Power
supply
Power
supply
Specifications
Fuse rating (A)
125 (IEC 60269-4)
160 (IEC 60269-4)
160 (IEC 60269-4)
160 (IEC 60269-4)
160 (IEC 60269-4)
200 (IEC 60269-4)
160 (IEC 60269-4)
200 (IEC 60269-4)
50 (IEC 60269-4)
50 (IEC 60269-4)
50 (IEC 60269-4)
50 (IEC 60269-4)
125 (IEC 60269-4)
125 (IEC 60269-4)
160 (IEC 60269-4)
L1/R
L2/S
L3/T
R0
T0