Omron M1 Series User Manual page 786

Multi-function compact inverter
Hide thumbs Also See for M1 Series:
Table of Contents

Advertisement

Appendices
Event name
Output Phase Loss Error
Meaning
There is an output phase loss.
Source
EtherCAT Master Function Mod-
ule
Error attrib-
Level
utes
Effects
User program
Indicators
EtherCAT NET RUN
---
System-de-
Variable
fined varia-
None
bles
Cause and
Assumed cause
correction
(1) The inverter's output wiring is
disconnected.
(2) The motor winding is broken.
(3) The inverter output terminals
are not firmly tightened.
Attached in-
None
formation
Precautions/
None
Remarks
A-240
Source details Slave
Minor fault
Recovery
Continues.
Operation
EtherCAT NET ERR
---
Data type
None
Correction
Measure the output current.
→ Replace the output wiring.
Measure the output current.
→ Replace the motor.
Check if there are loose screws
on the inverter output terminals.
→ Retighten the screws to the
recommended tightening torque.
Event code
28100000 hex
Detection tim-
ing
Error reset
Log category
Motor stops.
EtherCAT LINK/ACT
---
Name
None
Prevention
None
None
Tighten the screws to the recom-
mended tightening torque.
M1 Series EtherCAT Type User's Manual (I670)
Continuously
System log

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents