Table 3-6. Cooling Specifications - Advanced Energy VarioMatch Match Network VM 1000 Platform User Manual

Table of Contents

Advertisement

,&CAUTION:
Do not use de-ionized water for cooling purposes. De-ionized water
causes both corrosion and erosion of cooling manifolds.
Cooling specifications
Table 3-6.
Description
Cooling medium
Minimum water flow
Water pressure
Cooling water temperature
57020080-00D
AE VarioMatch
Match Network, VM 1000/1500 Platform
TM
Specification
Air-cooled (for units that show only "A" after the model
name or Air- and Water-cooled (for units that show "W" or
"AW"
after the model name)
1
1pm (0.26 gpm)
0.5 bar (7.25 psi) differential as required to achieve
minimum flow rate.
Maximum water pressure 4 bar (58 psi), maximum inlet,
not recommended for operation.
200C to 35
°
C. Cooling water temperature must always be
higher than ambient temperature to avoid condensation.
Specifications