AE recommends the following specifications for the water
used to cool the Navigator match network:
•
pH between 7 and 9
•
total chlorine <20 ppm
•
total nitrate <10 ppm
•
total sulfate <100 ppm
•
total dissolved solids <250 ppm
•
total hardness expressed as calcium carbonate
equivalent maximum 250 ppm
•
<250ppm
•
specific resistivity of 2500 Q/cm or higher at 25
•
total dissolved solids (TDS) as estimated by the
following:
TDS � 640,000/specific resistivity
Note: Do not use deionized water for cooling purposes in