Alarm Acknowledgement Facility (Aaf); Quiet Alarm - Panasonic MEW01349 Operating Instructions Manual

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01349
Rev: -
15.7
6.
6.
15.8
Operating Instructions Fire alarm system EBL512 G3, V1.1.x

Alarm Acknowledgement Facility (AAF)

One or more Alarm Acknowledgement Facility Controls
the system.
See EBL512 G3 Planning Instructions chapter "Alarm Acknowledge-
ment Facility (AAF)" for more information regarding the AAF
function.
During the Acknowledgement Period (10-60 sec.), the following
information (a list if many) is shown in the c.i.e. display:
AAF zone zz, activated
dd-mm-yyyy hh:mm
During the Investigation Period (0-3 min.), the following information
(a list if many) is shown in the c.i.e. display:
AAF zone zz, investigation in progress
dd-mm-yyyy hh:mm

Quiet alarm

One or more smoke detectors, via WinG3 programmed for Quiet
alarm, have passed the fire alarm level. Quiet alarm is used for fan
control (stop or start is depending on the type of fan).
Quiet alarm is normally used in conjunction with one I/O Matrix
board 4582, one application board for fan control
for fan control 3361, for control of each fan.
Indications and actions:
LEDs "Fire" (L1) are blinking (0.4 / 0.4 sec.), the buzzer sounds (0.8 /
5 sec.) and there is a Quiet alarm presentation (incl. a title "Quite
alarm") in the display:
24
The AAF Control is today available on the Australian market only.
25
The Fan control panel 4593 can be used for control of up to eight fans.
47
24
are used in
25
and one I/O unit

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ebl512 g3 v1.1.x

Table of Contents