Display Current Consumption On Com-Loop (H5/A5) - Panasonic MEW01777 Operating Instructions Manual

Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01777
27.5
Action
"
"
Menu
Scroll to menu H5.
"
"
Scroll to menu A5.
"
"
"
"
"
" or "
"
ESC
Rev: -
Display current consumption on COM-loop
(H5/A5)
The current consumption (an average value) for each COM loop can
be displayed.
NOTE! No or very small current consumption (< 10 mA) cannot be
presented correctly / precisely since the accuracy is ±5 mA.
Text in display
H5 Service
A1 Calibration of supervised output
A2 Sensitive fault detection mode
A3 Service mode for COM-loop
A4 Display current consumption in control unit
A5 Display current consumption on COM-loop
A6 Display statistics for communication
A7 Activate address setting mode for DU
A8 Setup wireless detectors
A9 SSD information
A5 Display current consumption on COM-loop
Display current consumption on COM-loop:
control unit: 00 (press ↵)
Please wait......
No reply from control unit.....
Current consumption on COM-loop: 0
control unit 00 is xxxx mA
A5 Display current consumption on COM-loop
Operating Instructions Fire alarm system EBL512 G3, V2.2.x
0
125
Comments
According to chapter
"Access", see page 88.
Write loop number and
control unit number and
press "
".
If the control unit don't
exist or don't answer.
The current consumption
accuracy is ±5 mA.
Info. automatically
th
updated each 5
second.
Scroll to another menu or
press "
".
ESC