2 Product Specifications

Specifications
Part number: 151095
Inputs: six universal inputs supporting 0-5 VDC, 4-20 mA, thermistor & contact closure. One
Input (UIN 7) to monitor monitoring 18-60 VDC
Outputs: two Form C digital outputs. Contact rating: 0.5 A @ 60 VDC
Network interface: Ethernet 10/100 Base-T
Protocols supported: IPv6, IPv4, HTTP, HTTPS, RADIUS Password Authentication, NTP, SMTP
(email), SNMP v1, v2c and v3 for Gets, Sets and traps/informs
Logging: Logs data for inputs, outputs and alarms
Alarm notification methods: TL1, Email and SNMP traps or informs
Alarm destinations: four programmable trap destinations, nine email addresses or distribution
lists
I/O terminal: spring loaded terminals supports 16 -24 AWG wire
Power: 24-48 VDC, 3.7 W max.
Battery: long life lithium (PN 250034) 3 VDC*
Ambient operating temperature: -4° to 140°F (-20° to 60°C), 0-95% RH Non-condensing
Certification: UL, cUL, FCC 47 CFR Part 15B, ISED ICES-003 Class A
Dimensions: 8.2" L x 4.7"W x 1.7" D (208 x 119 x 43 mm)
Weight: 0.9 lb. (408 g)
Warranty: 1 Year
Specifications subject to change without notice
Rev 3.0 9/15/22