--- 192.168.1.1 ping statistics ---
4 packets transmitted, 4 packets received, 0% packet loss
round-trip min/avg/max = 0.758/3.265/10.726 ms
10.8 Exit & Logout Command
The exit and logout command have the same function. Typing exit or logout will terminate your session
and if changes were made, will cause the system to reboot and come back up with the new settings.

11 File Upload Format

The MP1 supports complete programming by uploading a file through the web server. The file is broken
down into multiple segments and each starts with a heading in brackets. It is permissible to upload only
certain sections at a time, but when uploading a section, all the options for that section must be sent.
For example, if you send the [network] section, you must send all items in that section. For application
programs sections such as [alarms], you must send all alarm programs since the new uploaded alarm
section would replace all alarms that were in the unit. The alarms section [alarms] require that the
reference points (inputs, Modbus etc.) must be defined first. Therefore, they either have to be in the
same file during the upload or have previously been defined.
The configuration settings in each section are comma separated values. You can use a text editor or a
CSV application program to edit and or create the entire file or individual sections.
To become familiar with the file format, it is recommended that you download the file from the MP1 by
going to Settings/Advanced/Configuration Upload & Download and select "Download Configuration to
browser". A text file will be downloaded from the system to your web browser.

11.1 Section Formats

Listed below are the various sections in the configuration file along with explanation of what the section
is used for and how it correlates to programming through the web server.
11.1.1 [network]
Contains the network settings that are configured through the Settings/General section of the web
server for IPv4, IPv6 and IP General sections.
11.1.2 [site]
Site specific information from the Settings/General/Site Parameters section. In addition, there are fields
for latitude, longitude, and URL text information that are for future use and should not be changed.
11.1.3 [timeserver]
Information for setting the system clock which is configured through Settings/General/Time Settings.
11.1.4 [timezone]
The time zone used for the system which is configured through Settings/General/Time Settings.