Appendix A - SNMP Trap Format

®
The TELSEC
MP1 can send traps or informs to four different trap servers. The user can program the
system to send v1 traps, v2 traps/informs or v3 traps/informs to the server. When the MP1 sends a
trap, it will be sent with an OID based on the severity of the alarm. There will also be multiple variable
bindings (varabinds) sent to provide detailed information of the event that occurred. For proper trap
reception, you will need the alarm MIB. Please contact Quest for the current revision of the alarm MIB.
TRAP OIDs
The following table shows the available trap OID names and numbers for each trap type:
When a point goes into alarm, it will generate a trap using the critical, major, minor or info OID. Once
the alarm point goes out of alarm or clears, the MP1 will send a trap with the clear OID.
Trap Variable Bindings
The MP1 will send the following bindings with every trap that is sent:
Varabind Name
OID Number
sysUpTime
1.3.6.1.2.1.1.3
snmpTrapOID
1.3.6.1.6.3.1.1.4.1 Object
notifyProduct
11476.100.1.2
notifyCriticality
11476.100.1.3
notifyType
11476.100.1.4
notifyTime
11476.100.1.5
notifyName
11476.100.1.6
notifyValue
11476.100.1.7
notifyInputName
11476.100.1.8
notifySiteId
11476.100.1.9
Rev 3.0 9/15/22
Alarm Severity
OID Number
11476.100.0.5
Critical
11476.100.0.4
Major
11476.100.0.3
Minor
11476.100.0.2
Info
11476.100.0.1
Clear
Value Type
Timeticks
Identifier
Text String
Text String
Text String
Timeticks
Text String
Text String
Text String
Text String
OID Name
alarmCritical
alarmMajor
alarmMinor
alarmInfo
alarmClear
This binding is only available with v2 and v3 traps
and will contain the system up time since the
MP1 started up.
This binding is only available with v2 and v3 traps
and will contain the OID value for the alarm
severity.
The product type that is alarming. The value is
®
TELSEC
MP1
The alarm severity in Text. Available values are:
CRITICAL, MAJOR, MINOR, INFO and CLEAR
Alarm type. For TELSEC
SYS for inputs
The time the alarm was generated.
The thirty-two-character name of the alarm point
The text value of the sensor that caused the
alarm.
The thirty-two-character name of the input
referenced in the alarm point
The programmed site identification value for the