4 Local Operation

4.1 Power LED

®
Once the TELSEC
MP1 is installed, powered, and connected with an Ethernet connection, the system
will start operation based on the program controlling the unit. Under normal operation the green
Power LED will flash at one second intervals to indicate the system is operating properly. Occasionally
there may be a pause in this operation if the system is saving data to flash memory. If the LED is off for
longer than one minute, then check the power connection and cycle power to the unit. If the LED is
constantly on longer than a minute, then cycle power to the system to see if it goes back to normal
operation of flashing the LED.

4.2 Alarm LED

The red alarm LED will be illuminated when any of the alarm points are in alarm. This LED does not
provide notification of the state of the control relays since an alarm point may be in alarm, but not
associated with an output. If this LED is illuminated, then log into the web server on the MP1 and
review the active alarm log on the home page.

4.3 Relay Outputs

Relay outputs are programmable for normally energized or de-energized condition. The normally
open/normally closed terminations on the board refer to when the output is de-energized. There are
two outputs that may be associated with an alarm severity or a time schedule. Outputs that are
associated to an alarm severity will be "active" when the alarms are present and will deactivate when
either all alarms with the associated severity have cleared or if the acknowledge function is
used. Outputs associated with a time schedule will be "active" when the schedule is on and de-
activated when the schedule is off. Outputs can be bypassed indefinitely or for a period of time
remotely via the built-in web server or by SNMP SET commands.

4.4 Restoring to Factory Defaults

®
The TELSEC
MP1 has a small access hole next to the green power LED. Holding this switch in for
approximately 15 seconds during a power up (cycle power off then back on) will cause the system to
erase all programmed settings and go back to the factory defaults. During the Cold Start process, you
will see both the power LED and Alarm LED flash simultaneously every second. After a few seconds, the
alarm (red)LED will be illuminated solidly. Release the cold start switch once the alarm LED is on solid.
©