the chosen severity. The output will stay activated until the there are no longer any active alarms with
the chosen severity or if the Acknowledge button on the web page is pressed. Additionally, an input can
be used as the acknowledge function as well. When either Acknowledge function is activated, the
system will de-active the output. The output will remain deactivated until another active alarm with the
corresponding severity occurs. See Figure 44 below.
Figure 44 - Program Output Window
9.2.4
Output Acknowledge Function
The program output window has the option to select a digital input as an acknowledge function. If the
output is activated due to an Active Alarm, then the output will de-activate when the acknowledge input
is in the ON condition. This is useful when using a local enunciator panel that has a momentary input to
acknowledge the alarm condition and turn off the output. For example, you may program an output to
control a warning light when there is a critical alarm active and program another relay controlling the
horn. Pressing the acknowledge button could silence the horn until the next alarm occurs.
Figure 45 - Adding an Acknowledge Input
Press the Done button to go back to the program outputs page and then select another output to
program or press the Save Settings button.
©