The system will keep track of the number of alarms that are active for the input and display that as a
hyper link. Clicking on the link will bring up a window with a table of active alarms for the point.
The last column on the digital input page will show the defined "normal state" of the input. The purpose
of this column is to indicate how the point is defined to make trouble shooting easier without having to
navigate to the input definition page. The following will be displayed:
DRYNO = A normally open input wired between input and ground.
DRYNC = A normally closed point wired between input and ground
WETNO = A normally open input wired between the 24V terminal (or external voltage max 60 VDC)
and the input terminal.
WETNC = A normally closed input wired between the 24V terminal (or external voltage max 60 VDC)
and the input terminal.
6.1.2
Analog Inputs
Analog input status will show the input number, the programmed name for the point and the current
value of the input in the defined engineering units. The related alarms column will indicate the number
of active alarms currently present that reference the input. A number greater than 0 will be a hyperlink
that will bring up a window showing a table of active alarms for the point. Input seven is a special input
that is used to monitor the voltage of the incoming power to the MP1.
Rev 3.0 9/15/22
Figure 10 - Digital Input Status
Figure 11 - Analog Input Status
- 13 -
©
TELSEC
MP1 User Guide