Press the Save Settings button at the bottom of the page when completed. This will save any changes
made to the email dispatch and changes made to the SNMP dispatch.
8.2.3
Heartbeat Function
The MP1 can be enabled to send a heartbeat message based on a user defined interval. This is typically
used to coordinate with a monitoring system platform to ensure the system is operational. Heartbeat
messages are only sent via SNMP or TL1 over a Telnet/SSH connection. The heartbeat message is a user
definable 32-character message. Enter the desired message and select the interval by entering in the
number of seconds to wait between sending messages. A value of 0 will disable this function.
8.2.4
Test Alarms
The
button at the bottom of the page will cause a test trap to be sent to all the
defined destinations along with a test email to the defined recipients. The Test alarm will have a critical
severity with all the data fields showing TEST ALARM. The critical alarm will be followed by a clear alarm
again with all the data fields showing TEST ALARM.

8.3 HTTP User Administration

This page sets up the six available usernames for the password and what areas the user can access. If
the RADIUS server function is enabled, then this option does not affect user access. The default
passwords are the same as the username, but in all lower case. No characters are displayed in the
password field for security purposes. Passwords can be 5-32 characters in length and contain A-Z,a-z, 0-
9 and special characters _@#%*-
Rev 3.0 9/15/22
Figure 34 - Heartbeat Configuration
- 28 -
©
TELSEC
MP1 User Guide