Output Programming - Quest Controls TELSEC MP1 User Manual

Table of Contents

Advertisement

has created a special Excel spreadsheet for calculating the minimum and maximum values based on your
sensor output. Contact Quest to obtain a copy of this file for your use.
9.1.7
Log Type
Choose between TIME for a timed interval, COS for change of state or NONE to disable the logging for
the input. The TIME option is best for analog sensors to log on a user specified interval. Using COS for
digital inputs will optimize your logging to only put entries in the historical log when the point changes
its ON/OFF state. If you select COS for an analog input, the system will log whenever the input value
changes. Needless to say, this will fill up your log rather quickly if you decide to use COS on an analog
point.
9.1.8
Log Interval
This is the logging interval in minutes when you select a log type of TIME. The field will allow values
between 1 and 120 minutes for the interval.

9.2 Output Programming

The program outputs page will show the current settings for the two outputs. The output name is a
hyperlink that when clicked on will bring up the change settings window for that output.
9.2.1
Output Name
Enter up to thirty-two alphanumeric characters to name the output. The name is case sensitive and will
be displayed exactly as you typed it.
9.2.2
Default State
The default state is the condition of the relay when it is not being commanded to the active state. This
option allows for the relay coil to be either de-energized or energized as the default state of the relay.
Select whether the output should be De-energized when not activated (normal relay logic) or Energized
when not in the activated state (reverse relay logic).
9.2.3
Output Follows Option
Use the dropdown to select what function you want the relay to follow. This dropdown will show the
options of NONE meaning it will only be activated with a user bypass, Alarm severity options or defined
time schedules. Time schedules must be defined first for them to appear in the dropdown. By following
an alarm severity, the output will be in the activated (ON) condition when there is an active alarm with
Rev 3.0 9/15/22
Figure 43 - Output Settings Page
- 34 -
©
TELSEC
MP1 User Guide