Quest Controls TELSEC MP1 User Manual page 64

Table of Contents

Advertisement

Examples:
Command:
RTRV-ALM-ENV:::X123;
Response:
MP1_MONITOR 19-10-23 09:59:48
M X123 COMPLD
* 1 REPT ALM ENV
"ALM_A002:MN,BTL_LTMP,10-04,15-46-10:\"BLD002 LOW TEMPERATURE ALARM,ON\""
* 2 REPT ALM ENV
"ALM_A004:MN,BHL_LHUM,10-04,15-46-10:\"BLD011 LOW HUMIDITY ALARM,ON\""
;
Automatic TL1 Alarms
Once a point is determined to be in alarm, the controller will automatically send the alarm and log the event in the
alarm log. When the alarm goes away, the controller will automatically send out a clear message in TL1 format.
The clear will also be logged in the alarm log.
TL1 ALARM MESSAGE
FORMAT:
<cr><lf><lf>
<sp><sp><sp>TID<sp>YY-MM-DD<sp>HH:MM:SS<cr><lf>
ALMCDE<sp><ALARM SEQUENCE NUMBER><sp>REPT<sp>ALM<sp>ENV <cr><lf>
<sp><sp><sp>"ALM_<REF#>:<NOTIFICATION CODE>, <ALARM NAME>,MM-
DD,HH:MM:SS,<ALARMMESSAGE>"<cr><lf>
;
<ALMCDE>
*C = CRITICAL ALARM
** = MAJOR ALARM
*<sp> = MINOR ALARM
A<sp> = AUTOMATIC used for clear alarm and heartbeat messages
Rev 3.0 9/15/22
- 59 -
©
TELSEC
MP1 User Guide