<ALARM SEQUENCE NUMBER> = sequential sequence number assigned to every TL1 autonomous message.
<REF#>= The four-digit alarm reference number that was assigned when defining the alarm.
<NOTIFICATION CODE>
CR = Critical alarm
MJ = Major alarm
MN = Minor alarm
CL = Cleared alarm
NA = Non Alarm used for notifications.
<ALARM NAME> = The 32-character name that was defined for the alarm.
< ALARMMESSAGE> = The 32-character name of the point causing the alarm followed by a comma and the current
status of the alarm.
Sample alarm:
SITE401 19-10-26 11:43:39
** 1 REPT ALM ENV
"ALM_A005:MJ,POWER_Failure,10-26,11:43:39,COMMERCIAL POWER FAILURE"
;
Sample Clear Alarm:
SITE401 19-10-26 11:43:59
A 2 REPT ALM ENV
" ALM_A005:CL,POWER_Failure,10-26,11:43:59,COMMERCIAL POWER FAILURE"
;
Sample Heartbeat message:
RDNGPAREH72_MP1 19-10-23 09:48:05
A 13808 REPT EVT ENV
"HEARTBEAT:NA,HEARTBEAT,10-23,09-48-05:\"User defined Heartbeat message\""
;
Rev 3.0 9/15/22