Parts Replacement; Ecc800-Pro Common Operations; Preparations And Login - Huawei FusionModule2000-S User Manual

Smart modular data center
Hide thumbs Also See for FusionModule2000-S:
Table of Contents

Advertisement

FusionModule2000-S Smart Modular Data Center
User Manual

6.3 Parts Replacement

6.3.1 ECC800-Pro Common Operations

6.3.1.1 Preparations and Login

Prerequisites
Procedure
Step 1 Connect the PC network port and the WAN1 port (protected by a security
mechanism) on the ECC800-Pro using a network cable.
Table 6-13 Default IP addresses for the WAN and LAN ports on the ECC800-Pro
Port
WAN1
WAN2
LAN1 and LAN2
● In ECC800 V100R002C10 and earlier versions, the default IP address for the
● The WAN1 port IP address cannot be set to an IP address in any of the
● IP addresses for the WAN1 and WAN2 ports should not be set in the same
● In some customized scenarios, the default IP address for the WAN2 port is
● The WAN port supports Internet access, and the LAN port supports LAN access.
Step 2 Configure the PC IP address and the WAN1 IP address in the same network
segment.
Issue 07 (2022-09-30)
Supported operating system: Windows 7 and later versions
Recommended screen resolution: 1366 x 768 or higher
Browser: Chrome, Firefox, Internet Explorer 11 or later
NO TICE
WAN1 port is 192.168.1.10.
following network segments: 192.168.0.x, 192.168.245.x, 192.168.246.x and
192.168.248.x.
network segment.
192.168.248.10. The default value may vary.
Connect the PC network port to the WAN1 port or LAN port on the ECC800-Pro
based on the access network.
Copyright © Huawei Technologies Co., Ltd.
Default IP Address
192.168.8.10
192.168.0.10
192.168.248.10 (FusionModule800)
192.168.248.10
6 Operation and Maintenance
298

Advertisement

Table of Contents
loading

This manual is also suitable for:

V100r021c10

Table of Contents