FusionModule2000-S Smart Modular Data Center
User Manual
Table 5-24 DIP switch settings for T/H sensors
T/H Sensor
Address
1
2
3
4
5
6
Step 2 Add a T/H sensor.
1.
2.
3.
Issue 07 (2022-09-30)
NO TE
● The numbers 1–6 indicate the DIP switch settings of the T/H sensors.
● After the addresses are set, power on the device, choose Settings > System Settings >
T/H Sensor on the home screen, and set the sensors in the aisles corresponding to the
addresses to Enable. Otherwise, the sensors will not work.
DIP
Switch
1
ON
OFF
ON
OFF
ON
OFF
Log in to the ECC800-Pro WebUI as an administrator.
Add a T/H sensor.
Table 5-25 Adding a T/H sensor
Path
Parameter
Choose
Device
System
Attribute
Settings >
Device Type
Device
Management
and click Add
Connect To
Device. The
parameters
Communica
for adding
tions Port
devices are
displayed.
Device
Address
Click Test Connect to check whether the T/H sensor connects to the ECC800-
Pro properly.
Copyright © Huawei Technologies Co., Ltd.
DIP
DIP
Switch
Switch
2
3
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
OFF
ON
ON
ON
Value
Select Sensor from the drop-down list box.
Select T/H sensor from the drop-down list
box.
Select ECC800 from the drop-down list box.
Select COM1 from the drop-down list box.
NOTE
The setting example indicates that the T/H sensor
is connected to the COM1 port on the ECC800-
Pro. If the T/H sensor is connected to another
port, select the number of the connected port.
In this example, Device Address is set to 1.
During actual configuration, set the device
address for the T/H sensor based on the
actual situation.
5 Power-On Commissioning
DIP
DIP
Switch
Switch
4
5
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
DIP
Switch
6
OFF
OFF
OFF
OFF
OFF
OFF
201