Huawei FusionModule2000-S User Manual page 147

Smart modular data center
Hide thumbs Also See for FusionModule2000-S:
Table of Contents

Advertisement

FusionModule2000-S Smart Modular Data Center
User Manual
Figure 5-1 Settings Wizard
Step 2 After you set parameters on the Settings Wizard screen, the system displays the
Bypass mode and No battery alarms, which do not need to be handled. Other
alarms need to be handled.
Issue 07 (2022-09-30)
NO TE
● Set the time and date correctly. Incorrect time and date will cause false fault analysis
during maintenance or repair, affecting the normal operation.
● After you set network parameters, connect the UPS to the network over a network
cable, which allows you to remotely manage the UPS. If you do not need remote
management, retain the default network parameter settings.
NO TE
● After you set parameters on the Settings Wizard screen, choose System Info > Settings
> System Settings. Check that Requisite modules and Redundant modules match the
actual values.
● If dry contact signals are connected to the system, choose System Info. > Settings >
Dry Contact Set. Check that the connected dry contacts have been enabled and that
the disconnected dry contacts have been disabled.
Copyright © Huawei Technologies Co., Ltd.
5 Power-On Commissioning
136

Advertisement

Table of Contents
loading

This manual is also suitable for:

V100r021c10

Table of Contents