Step 3 If the system has connected to the remote EPO switch, choose System Info. >
Settings > System Settings and set EPO detection to Enable.
Step 4 View the system running diagram on the LCD to check that the UPS is working in
bypass mode.
----End

5.1.1.4 Starting the Inverter

UPS System User List
Table 5-3 UPS system user list
Default User
admin (administrator)
operator (common user)
Starting the Inverter on the LCD
Step 1 Choose Common Functions > Inv. ON.
Step 2 In the displayed login screen, select a user name and enter the password.
Step 3 In the displayed dialog box, tap Yes to start the inverter.
----End

5.1.1.5 Powering On Loads

Context
After the inverter starts, the UPS transfers to inverter mode, and the Bypass mode
alarm on the LCD disappears.
Procedure
Step 1 After confirming that the battery strings are properly connected, turn on the
battery string input switch. If there are multiple battery strings, turn on the switch
for each battery string and then the general switch between battery strings and
the UPS. After you turn on the battery string input switch, the No battery alarm
disappears.
Step 2 Switch on the UPS output circuit breaker QF3.
Issue 07 (2022-09-30)
NO TE
You can also start the inverter by choosing System Info > Maintenance > Inv. ON.
Copyright © Huawei Technologies Co., Ltd.
Preset Password
000001
000001
5 Power-On Commissioning
Permission Description
Can set all the menus.
Can only view
parameters and set some
parameters.