FusionModule2000-S Smart Modular Data Center
User Manual
Figure 3-103 Connecting a T/H sensor cable
Step 2 Set the DIP switch on the T/H sensor. For details, see
Table 3-3 DIP switch settings on T/H sensors
Locati
on
Cold
aisle
● The default address of T/H sensors purchased is 1.
● Keep the last RS485_R DIP switch in OFF position.
● After the addresses are set, power on the device, choose Settings > System
Step 3 Connect the T/H sensor cable. Secure the T/H sensors inside the cabinet at the
return air side of the smart cooling product and connect their IN ports to the main
control board. When connecting the T/H sensors outside the cabinet, connect the
Issue 07 (2022-09-30)
Display Name
Cold aisle 1
temp/humid
NO TICE
Settings > T/H Sensor on the home screen, and set the sensors in the aisles
corresponding to the addresses to Enable. Otherwise, the sensors will not work.
Copyright © Huawei Technologies Co., Ltd.
Addr
DIP Switch No.
ess
1
2
11
ON
ON
3 Hardware Installation
Table
3-3.
3
4
5
OFF
ON
OFF
6
OFF
110