FusionModule2000-S Smart Modular Data Center
User Manual
Tab
T/H Sensor
Issue 07 (2022-09-30)
Parameter
Floor water overflow
alarm action
In-cabinet water
overflow alarm action
Temperature and
humidity control type
Temperature setpoint
Copyright © Huawei Technologies Co., Ltd.
5 Power-On Commissioning
Description
Set the action of the device if there is
water overflow on the floor based on
the actual scenario.
● Shutdown: The device shuts down
when a floor water overflow alarm
is generated.
● Inactivity: The device runs as usual
when a floor water overflow alarm
is generated.
● Only indoor fan running: Only the
indoor fan runs when a floor water
overflow alarm is generated.
● Humidifier stopped: Only the
humidifier is stopped when a floor
water overflow alarm is generated.
Set the action of the device if there is
water overflow in the cabinet based on
the actual scenario.
● Shutdown: The device shuts down
when an in-cabinet water overflow
alarm is generated.
● Inactivity: The device runs as usual
when an in-cabinet water overflow
alarm is generated.
● Only indoor fan running: Only the
indoor fan runs when an in-cabinet
water overflow alarm is generated.
● Humidifier stopped: Only the
humidifier is stopped when an in-
cabinet water overflow alarm is
generated.
When the application scenario is non-
aisle containment, you are advised to
choose Return air. Choose Cold aisle
if cold aisle T/H sensors are installed.
Hot aisle is not recommended.
After the temperature and humidity
control type and the temperature
value under this type are set, the
device performs regulation based on
the settings.
● Return air: 26–35°C recommended
● Supply air: 18–24°C recommended
● Cold aisle: 18–24°C recommended
● Hot aisle: 26–35°C recommended