2.3 Field Requirements

To prevent condensation, a dehumidifier must be installed in the equipment room
when the dew point temperature is higher than 18°C (temperature: 18°C,
humidity: 100% RH; temperature: 27°C, humidity: 57% RH).
Figure 2-1 Space requirements for a simplified single-row MDC
Issue 07 (2022-09-30)
NO TICE
NO TE
● The cabinet layouts shown in the figures are for ease of description and do not provide
reference for engineering layout.
● The cold and hot aisle containment of nine standard cabinets is used as an example in
this document, which supports a maximum deployment of 24 IT cabinets.
● If the site conditions do not meet the field requirements, contact technical support.