Adapting The Status Signal; Overview Of Diagnostic Information - Endress+Hauser Proline Prosonic Flow E 100 HART Operating Instructions Manual

Ultrasonic time-of-flight flowmeter
Table of Contents

Advertisement

Proline Prosonic Flow E 100 HART
Endress+Hauser
12.5.2

Adapting the status signal

Each item of diagnostic information is assigned a specific status signal at the factory. The
user can change this assignment for specific diagnostic information in the Diagnostic
event category submenu.
Expert → Communication → Diagnostic event category
Available status signals
Configuration as per HART 7 Specification (Condensed Status), in accordance with
NAMUR NE107.
Symbol
Meaning
Failure
A device error is present. The measured value is no longer valid.
A0013956
Function check
The device is in service mode (e.g. during a simulation).
A0013959
Out of specification
The device is being operated:
• Outside its technical specification limits (e.g. outside the process temperature range)
• Outside of the configuration carried out by the user (e.g. maximum flow in parameter
A0013958
20 mA value)
Maintenance required
Maintenance is required. The measured value is still valid.
A0013957
Has no effect on the condensed status.
A0023076
12.6

Overview of diagnostic information

The amount of diagnostic information and the number of measured variables affected
increase if the measuring device has one or more application packages.
In the case of some items of diagnostic information, the status signal and the
diagnostic behavior can be changed. Change the diagnostic information →  76
Diagnostic
Short text
number
Diagnostic of sensor
022
Temperature sensor
defective
082
Data storage
083
Memory content
104
Sensor signal path 1 to n 1. Check process conditions
105
Downstream transducer
path 1 to n defective
Diagnostics and troubleshooting
Remedy instructions
1. Replace sensor electronic module
(ISEM)
2. Replace device
1. Check module connections
2. Contact service
1. Restart device
2. Restore HistoROM S-DAT backup
(' D evice reset' parameter)
3. Replace HistoROM S-DAT
2. Replace sensor electronic module
(ISEM)
3. Replace device
Replace device
Status
Diagnostic
signal
behavior
[from the
[from the
factory]
factory]
F
Alarm
F
Alarm
F
Alarm
F
Alarm
F
Alarm
77