Installation
18
Outlet runs when installing external devices
If installing an external device, observe the specified distance.
PT
Pressure
Installation dimensions
For the dimensions and installation lengths of the device, see the "Technical
Information" document, "Mechanical construction" section.
6.1.2

Requirements from environment and process

Ambient temperature range
Transmitter
Local display
Sensor
If operating outdoors:
Avoid direct sunlight, particularly in warm climatic regions.
System pressure
It is important that cavitation does not occur, or that gases entrained in the liquids do not
outgas.
Cavitation is caused if the pressure drops below the vapor pressure:
In suction lines
Ensure the system pressure is sufficiently high to prevent cavitation and outgassing.
For this reason, the following mounting locations are recommended:
• At the lowest point in a vertical pipe
• Downstream from pumps (no danger of vacuum)
Thermal insulation
In the case of some fluids, it is important to keep the heat radiated from the sensor to the
transmitter to a low level. A wide range of materials can be used for the required
insulation.
3...5 × DN
–25 to +60 °C (–13 to +140 °F)
–20 to +60 °C (–4 to +140 °F), the readability of the display may be
impaired at temperatures outside the temperature range.
–25 to +60 °C (–13 to +140 °F)
Proline Prosonic Flow E 100 HART
PT
Endress+Hauser
A0015901