Endress+Hauser Proline Prosonic Flow E 100 HART Operating Instructions Manual page 50

Ultrasonic time-of-flight flowmeter
Table of Contents

Advertisement

Commissioning
Parameter
Operating mode
Assign frequency output
Minimum frequency value
Maximum frequency value
50
Parameter overview with brief description
Prerequisite
The Frequency option is
selected in the Operating
mode parameter (→  49)
parameter.
In the Operating mode
parameter, the Frequency
option is selected, and one of
the following options is
selected in the Assign
frequency output parameter
(→  50):
• Volume flow
• Mass flow
• Sound velocity
• Flow velocity
• Temperature
• Acceptance rate
• Signal strength
• Signal to noise ratio
• Turbulence
• Signal asymmetry
In the Operating mode
parameter, the Frequency
option is selected, and one of
the following options is
selected in the Assign
frequency output parameter
(→  50):
• Volume flow
• Mass flow
• Sound velocity
• Flow velocity
• Temperature
• Acceptance rate
• Signal strength
• Signal to noise ratio
• Turbulence
• Signal asymmetry
Description
Define the output as a pulse,
frequency or switch output.
Select process variable for
frequency output.
Enter minimum frequency.
Enter maximum frequency.
Proline Prosonic Flow E 100 HART
Selection / User
Factory setting
entry
• Pulse
Pulse
• Frequency
• Switch
• Off
Off
• Volume flow
• Mass flow
• Sound velocity
• Flow velocity
• Temperature
• Acceptance rate
• Signal strength
• Signal to noise
ratio
• Turbulence
• Signal asymmetry
0.0 to 10 000.0 Hz
0.0 Hz
0.0 to 10 000.0 Hz
10 000.0 Hz
Endress+Hauser